Self-supporting LV-ABC Cables(Franch Standard)
Aluminium conductors with XLPE insulation,standards:NFC 33-209
Dimensions of conductors
Cross section(mm²) |
Stranded |
DC resistance Ω/km |
Conductor diameter |
Thickness of insulation (mm) |
Core diameter |
carrying capacity |
Breaking load (kN) |
||
Min.(mm) |
Max.(mm) |
Min.(mm) |
Max.(mm) |
||||||
16 |
7 |
1.91 |
4.6 |
5.1 |
1.2 |
7.0 |
7.8 |
- |
1.9 |
25 |
7 |
1.20 |
5.8 |
6.3 |
1.4 |
8.6 |
9.4 |
112 |
3.0 |
35 |
7 |
0.868 |
6.8 |
7.3 |
1.6 |
10.0 |
10.9 |
138 |
- |
50 |
7 |
0.641 |
7.9 |
8.4 |
1.6 |
11.1 |
12.0 |
168 |
- |
70 |
12 |
0.443 |
9.7 |
10.2 |
1.8 |
13.3 |
14.2 |
213 |
- |
95 |
19 |
0.320 |
11.0 |
12.0 |
1.8 |
14.6 |
15.7 |
258 |
- |
120 |
19 |
0.253 |
12.0 |
13.1 |
1.8 |
15.6 |
16.7 |
306 |
- |
150 |
19 |
0.206 |
13.9 |
15.0 |
1.7 |
17.3 |
18.6 |
344 |
- |
Dimensions of Neutral conductors
Cross section(mm²) |
Conductor structure No./mm |
DC resistance Ω/km |
Conductor outer direction |
Conductor diameter |
Thickness of insulation |
Core diameter |
Breaking load (kN) |
||
Min.(mm) |
Max.(mm) |
Min.(mm) |
Max.(mm) |
||||||
54.6 |
7/3.15 |
0.63 |
|
9.2 |
9.6 |
1.6 |
12.3 |
13.0 |
16.6 |
70 |
7/3.50 |
0.50 |
10.0 |
10.2 |
1.5 |
12.9 |
13.6 |
20.5 |
|
95 |
19/2.50 |
0.343 |
12.2 |
12.9 |
1.6 |
15.3 |
16.3 |
27.5 |
Test line
Cross section(mm²) |
Stranded |
DC resistance Ω/km |
Conductor outer direction |
Conductor diameter |
Thickness of insulation |
Core diameter |
Breaking load (kN) |
||
Min.(mm) |
Max.(mm) |
Min.(mm) |
Max.(mm) |
||||||
1.5 |
1 |
12.1 |
- |
- |
1.5 |
1.2 |
3.7 |
4.2 |
- |
PRODUCT TEST REPORT
Description | ABC CABLE |
specification |
ABC 3*50+54.6 |
|||||
|
NFC 33 209 |
|
KM |
|||||
No. |
Properties |
Standard requirements |
|
|
|
|
||
1 |
Manufacturer |
LAURENCE |
LAURENCE |
√ |
- |
|||
2 |
Nominal voltage(U0/U) |
0.6/1 |
kV |
0.6/1 |
√ |
- |
||
3 |
Phase |
|||||||
3.1 |
Number of cores |
1 |
1 |
√ |
Visual measurement |
|||
3.2 |
Cross section |
50 |
mm² |
50 |
√ |
- |
||
3.3 |
Diameter of conductor |
8.1±1% |
mm |
8.2 |
√ |
Vernier caliper |
||
3.4 |
Nominal Thicknes |
1.6 |
mm |
1.7 |
√ |
Projector |
||
3.5 |
Minimum Thicknes |
1.34 |
mm |
1.45 |
√ |
Projector |
||
3.6 |
|
11.5 |
mm |
11.6 |
√ |
Vernier caliper |
||
3.7 |
resistance at 20 ℃.max |
0.641 |
Ω/km |
0.630 |
√ |
DC bridge |
||
4 |
Neutral |
|||||||
4.1 |
Conductor structure |
7/3.15 |
No./mm |
7/3.15 |
√ |
Visual measurement |
||
4.2 |
Diameter of AL wire |
3.15±1% |
mm |
3.16 |
√ |
Micrometer |
||
4.3 |
Diameter of conductor |
9.45±1% |
mm |
9.45 |
√ |
Vernier caliper |
||
4.4 |
Nominal Thicknes |
1.6 |
mm |
1.7 |
√ |
Projector |
||
4.5 |
Minimum Thicknes |
1.34 |
mm |
1.47 |
√ |
Projector |
||
4.6 |
diameter of core |
12.65 |
mm |
12.70 |
√ |
Vernier caliper |
||
4.7 |
Rated Strength |
16600 |
N |
16693 |
√ |
Tensile testing machine |
||
4.8 |
DC resistance at 20 ℃.max |
0.63 |
Ω/km |
0.60 |
√ |
DC bridge |
||
5 |
Cable |
|||||||
5.1 |
diameter of bundle |
28.3±1% |
mm |
28.5 |
√ |
Vernier caliper |
||
5.2 |
Laying up direction |
Right |
Right |
√ |
Visual measurement |
|||
5.3 |
Lay |
430~590 |
mm |
500 |
√ |
Ruler |
||
5.4 |
Voltage test |
3.5kV/5min |
kV |
3.5kV/5min |
√ |
AC voltage test system |
||
Results |
Comply with standard and allow shipment. |